  • Set up your own cloud-native simulation in minutes.

  • Indoor Thermal Standards: What’s The Difference Between ASHRAE 55 AND ISO 7730?

    Jon Wilde
    BlogArchitecture, Engineering & Construction (AEC)Indoor Thermal Standards: What’s The Difference Between ASHRAE 55 AND ISO 7730?

    Achieving thermal comfort needs to address the ergonomics of a thermal environment. Ergonomics, a post-1940’s term for the study of people’s efficiency in their working environment, shape the laws and regulations around indoor working conditions across the globe. By definition, this must take into consideration factors such as equipment and facilities, work processes, the environment, management systems; all boiling down to a systematic process of designing for human use. 

    This systematic process that assesses thermal comfort is utilized in both the ASHRAE 55 and the ISO 7730 standards, and is derived from the calculation of the predictive mean vote (PMV) and the predicted percentage of dissatisfied (PPD) index to determine an acceptable range of thermal conditions for human occupancy. Our question is, how are these standards employed across the world, and how do acceptable thermal comfort ranges differ between the standards? In this article, we will explore the similarities and differences between the ASHRAE 55 and ISO 7730 standards.

    When are ASHRAE 55 and ISO 7730 Employed As Standards?

    Both standards cover the evaluation of modern, indoor, thermal environments including residential and industrial. They both provide definitions, requirements, and parameters that need to be met within a certain range to predicted an operative temperature and, ultimately, thermal comfort.

    thermal comfort with simscale

    These standards can be employed for existing buildings as well as new builds in the design phase. Compliance with these standards can be ensured already from the design phase or renovation planning, which is why simulation using platforms like SimScale are invaluable to engineers. The strictness of the compliance range, however, differs for existing structures vs. new buildings, with lower requirements being applied for existing spaces.

    How are PMV and PPD Employed in Each Standard?

    Although both standards go beyond these calculations when it comes to defining comfort, they require PMV to be calculated, which is then used then determine the range within the PPD index. In order to comply with ASHRAE 55, the thermal limit on the 7-point scale of PMV is between -0.5 and 0.5.

    pmv index
    The 7 point PMV scale

    ISO 7730 elaborates on this limit, giving several indoor environments ranges. ISO defines the hard limit as ranging between -2 and +2, while for old buildings the acceptable comfort limits range  between -0.7 and +0.7, and new buildings between -0.5 and +0.5.

    pmv and ppd graph
    Calculating PPD from PMV

    PPD can range from 5% to 100%, depending on the estimated PMV. These comfort values will fluctuate depending on where the occupant is located within the given space. For comfort ranges to comply with standard criteria, no occupied point in space should be above 20% PPD (corresponding to the -0.5 to +0.5 range).

    What Are Key Differences Between the Two Standards?

    The two standards essentially cover the same variables, calculations, and ranges, but do differ in a few respects. ASHRAE, or the American Society of Heating, Refrigerating, and Air Conditioning Engineers, first published the 55 standard in 1966 and has continuously updated it every 3-7 years. While this standard is internationally intended, it is most well recognized within the United States. ISO, or the International Organization for Standardization, is a worldwide federation of national standards bodies, and is, therefore, broader and encompassing of more standards but at a less specified level. Each organized body has a series of standards that will be discussed below.

    The ISO Series Vs. The ASHRAE Series

    The ISO 7730 standard was developed in parallel with ASHRAE 55, but is part of a series of ISO standards that are reviewed every 5 years and cover a range of thermal environments from mild to extreme. For example:

    ISO 7243– This standard is used for hot environments, and is the assessment of heat stress using the WBGT (wet bulb globe temperature) index.

    ISO 7933– This standard describes a method for predicting the sweat rate and the internal core temperature that the human body will develop in response to the working conditions, also for hot environments.

    ISO/TR 14415– This standard explains the application of international standards for thermal comfort for people with special requirements (i.e., those with physical disabilities).

    iso 7730 standard

    While the ISO series focuses on thermal comfort and expands upon the variables mentioned in ISO 7730 (metabolic rate, heat, etc.), the ASHRAE series has more documents pertaining to other HVAC applications. For example:

    ASHRAE Standard 15– This document covers safety standards for refrigeration systems.

    ASHRAE Standard 34– This standard is used for the designation and safety classification of different refrigerants used in HVAC systems.

    ASHRAE Standard 100– This standard focuses on energy efficiency in existing buildings.

    Scope Differences

    The scope determined in both documents addresses the same environmental (temperature, thermal radiation, humidity, airspeed) and personal factors (level of activity, clothing insulation). ISO 7730 goes further to mention that cultural, national, and geographical differences need to be taken into account when evaluating non-air conditioned buildings, because it is more internationally recognized.

    Terminology Differences

    The documents have some terminology inconsistencies, as ISO has an additional standard (1371) that covers thermal environment vocabulary and symbols. For example, when considering non-steady-state environments ISO 7730 defines ‘drift temperature’ as the passive monotonic, steady, non-cyclic change in the operative temperature of a space, and defines ‘ramp temperature’ as the same but as an active change, but fails to give a defined time period to mark this cyclic variation. ASHRAE 55 does not define these terms, but in section 5.2.5.1 defines that the temperature changes are treated as such if the time period exceeds 15 minutes. While ISO 7730 and ASHRAE 55 both include their key terminology in section 3, ASHRAE 55 has a more comprehensive list within the document itself.

    pmv_calculation
    ISO 7730’s provided calculation for PMV for a specific environment (Source)

    Naturally Ventilated Space Differences

    While ASHRAE 55, specifically since the 2004 updated version, gives many liberties to naturally ventilated spaces (i.e., Section 5 states that temperature fluctuations under the control of occupants have no negative effect on thermal comfort and therefore do not need to adhere to certain requirements mechanically ventilated spaces need to), ISO 7730 doesn’t discuss it.

    Compliance Differences

    ASHRAE 55 Section 6 is dedicated to prescribing what engineers need in order to comply with the standard. Given ranges for each index must be met and additional influencing conditions must be acknowledged. Achieving thermal comfort of an environment is an innately cumbersome task, but ASHRAE 55 provides the variable tables, equations, thermal environment survey, and even sample compliance documentation to make adhering to the standard as straightforward as possible. The criteria for compliance is not mentioned in ISO 7730.

    Conclusion

    No matter what standard you adhere to for your design, PMV and PPD must be calculated, and this can be done with the help of SimScale. While PMV and PPD are important to determine whether the building complies with either of the standards, they are not the only aspects to consider when determining thermal comfort compliance. To name a few other aspects, mentioned in the standards, draught, radiation asymmetry, whether the flow is controlled or not, and more should also be accounted for. In other words, they are helpful tools, but not necessarily the whole toolbelt.

    If you’re building a structure in the United States with a natural or hybrid ventilation unit, ASHRAE 55 will most likely be a better compliance fit. If you’re updating a building in Europe and want to evaluate more extreme non-steady-state thermal environments, ISO 7730 should be your standard. The base source code which we use to calculate the values for PMV and PPD is the same in both of the standards.

    Additional Thermal Comfort Resources From SimScale